Multimedia Filtration (AQMF)
Aquamat’s Multimedia Filtration (AQMF) plants are designed to treat ground water, surface water, tertiary treated effluent, storm water or wastewater with <30 mg/L of total suspended solids. Standard filtration media includes high grade zeolite media for suspended solids removal, granular activated carbon (GAC) for removal of organics, colour, odour or chlorine and Iron removal media for dissolved iron and manganese. Additional filtration media, such as calcite for hardness correction and various ion exchange resins, are available on request. Additional pre-filtration and post-filtration treatment steps may be added as required to suit feed water conditions and/or treated water quality requirements. The plants are available as skid mounted or containerised systems.
GROUND WATER
SURFACE WATER
INDUSTRIAL WATER
CUSTOM REQUIRED FLOW RATES AND PROCESSES ARE AVAILABLE. JUST ASK US.
Data Sheets
Parameter | Units | AQMF 12 |
AQMF 24 |
AQMF 50 |
AQMF 90 |
AQMF 140 |
AQMF 240 |
AQMF 500 |
AQMF 1000 |
AQMF 1500 |
AQMF 2500 |
AQMF 4000 |
AQMF 7000 |
|
Filtration flow rate | m³/day | 12 | 24 | 50 | 90 | 140 | 240 | 500 | 1000 | 1500 | 2500 | 4000 | 7000 | |
m³/h | 0,5 | 1 | 2,1 | 4 | 6 | 10 | 21 | 42 | 63 | 106 | 170 | 300 | ||
Required voltage | V | 450 V, 3 Phase, 50Hz (AC 220V, 1 Phase for AQMF 12 140) (220 V AC, Single phase, 50 Hz) | ||||||||||||
Recovery Rate | % | 90 – 98% (Varies on type of filtration media and feedwater quality | ||||||||||||
Service flow rate |
||||||||||||||
Zeolite | m·h−1 | 20 | (Typical, might vary depending on feedwater quality) | |||||||||||
AFM | 10 | |||||||||||||
Greensand | 10 | |||||||||||||
Iron removal media | 10 | |||||||||||||
GAC Media | 10 | |||||||||||||
Backwash flow rate |
||||||||||||||
Zeolite | m·h−1 | 40 | ||||||||||||
AFM | 40 | |||||||||||||
Greensand | 25 | |||||||||||||
Iron removal media | 25 | |||||||||||||
GAC Media | 25 | |||||||||||||
Protection | Natural elements | – | Needs to be protected from natural elements (Control boxes are IP65 rated) |
Parameter | Units | Zeolite | AFM | Greensand | Iron removal | GAC | |||||
Feedwater | Filtrate | Feedwater | Filtrate | Feedwater | Filtrate | Feedwater | Filtrate | Feedwater | Filtrate | ||
Temperature | oC | 5 – 40 | 5 – 40 | 5 – 40 | 5 – 40 | 5 – 40 | |||||
Total Suspended Solids (TSS) | mg/L | <30 | <1 | <5 | <1 | <5 | <5 | <5 | <5 | <5 | <5 |
Turbidity | NTU | <15 | <5 | <5 | <5 | <5 | <5 | <5 | <5 | <5 | <5 |
Filtration Degree | Um | 5 | – | – | – | – | |||||
Dissolved iron | mg/L | – | – | – | – | <10 | <0.1 | <5 | <0.1 | – | – |
Dissolved manganese | mg/L | <2 | <0.1 | <0.5 | <0.1 | ||||||
Total Organic Carbon (TOC) | mg/L | – | – | – | – | – | – | – | – | <10 | <0.1 |
Colour | HCU | – | – | – | – | – | – | – | – | Up to 98% reduction | |
Trihalomethanes | ug/L | – | – | – | – | – | – | – | – | <1,000 | <250 |
Equipment | AQMF 25 | AQMF 50 | AQMF 150 | AQMF 250 | AQMF 500 | AQMF 1000 | AQMF 1500 | AQMF 2500 | AQMF 4000 | |
Skid Mounted Plant & Equipment | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | |
Filter & Backwash Pump | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Premium Pump Package | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Duty/standby pumps for redundancy | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Variable speed drives for pumps | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Containerised with ventilation & lights | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Container side access door | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Premium Siemens PLC with touch screen HMI | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
uPVC pipework & fittings | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | |
Auto backwashing FRP filter vessel(s) | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Standard Instrumentation Package | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ | |
Premium Instrumentation Package | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Disinfection | UV Steriliser | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ |
Chlorination | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Product Water Quality Monitoring | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Feedwater buffer storage | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Product water buffer storage | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Product water distribution | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | ⊚ | |
Key | ||||||||||
Included | ☑ | |||||||||
Optional | ⊚ | |||||||||
Not applicable | N/A |
To proceed with a final design for guaranteed AQMF performance and product water quality, a water analysis will be required of your feedwater to determine the extent of treatment required to meet the AQMF and product water specifications.
Instrumentation & Controls | Sediment filtration | Iron removal filtration | Activated Carbon adsorption | |||
Standard | Premium | Standard | Premium | Standard | Premium | |
Pressure gauges on inlet/outlet manifolds | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ |
Raw water & Product storage float level switches | ☑ | N/A | ☑ | N/A | ☑ | N/A |
Raw water & Product storage level transmitters | N/A | ☑ | N/A | ☑ | N/A | ☑ |
Timer operated backwash | ☑ | N/A | ☑ | N/A | ☑ | N/A |
Pressure switch to activate backwash | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ |
Chemical dosing tank low level switches | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ |
Pressure transmitters on inlet/outlet manifolds | N/A | ☑ | N/A | ☑ | N/A | ☑ |
Flow transmitter after filtration | N/A | ☑ | N/A | ☑ | N/A | ☑ |
Turbidity analysier after filtration | N/A | ☑ | N/A | ☑ | N/A | ☑ |
ORP analyser | ☑ | ☑ | ☑ | ☑ | ☑ | ☑ |
Remote monitoring option | N/A | ☑ | N/A | ☑ | N/A | ☑ |